Fire & Smoke Dampers

IBD-FS
Fire Dampers – Fire Seal Curtain

The Holyoake IBD-FS fire seal curtain-type fire dampers are designed to preserve the integrity of a building while allowing air distribution systems to function seamlessly. These dampers facilitate the passage of air while effectively containing fire, smoke, and toxic gases. Featuring interlocking galvanised steel blades and stainless steel side seals, these dampers are housed within a galvanised steel guide channel frame. This compact design minimises space requirements and ensures straightforward installation in ductwork.

IBD-FS Fire Dampers Rating

IBD-FS leakage-rated, fire dampers have undergone rigorous testing in accordance with AS 1530.4 – 2014 and has comfortably met the stringent leakage integrity rates of 11.6.2.1, aligned with the European ISO Standard 10294-1 ‘E’ Classification.

In fire rating tests conducted according to Standard AS 1530.4 – 2014, the IBD-FS fire dampers demonstrated exceptional integrity for over 4 hours. Compliant with the Australian Construction Code and New Zealand Building Code, they hold an impressive Fire Resistance Level (FRL) or Fire Resistance Rating (FRR) of –/240/–, making them a trusted choice for fire safety in your projects.

  • Tested to AS 1530.4:2014 achieving a four hour fire rating.
  • Passed leakage integrity rates based on ISO 10294-1 ‘E’ Classification.
  • Single sections available up to 1200mm (wide) x 1200mm (high).
  • Multiple sections available up to 3600mm (wide) x 2400 (high) in a 3×2 configuration.
  • Multiple ducted connections are available in a multiple section damper configuration.
  • Installation permitted in both the horizontal and vertical plane (specify when ordering).
  • Airflow and fire rated from either direction when installed in a wall.
  • Electro thermal resettable links are available for remote triggering.
  • A range of duct connection styles are available.
  • Available in stainless steel as an option.
Revit Files